SF6 insulated RMU for indoor use

Up to 24 kV

630 A

25 kA

Catalogue

Instructions Manual

 

FLUOFIX® GC is a type tested SF6 insulated compact distribution Ring Main Unit, with integrated protection (optional).

 

This unit is particularly suitable to industrial (dust, sand), tropical, arid or salty environments. All live parts are protected against environment agents inside a sealed for life stainless steel tank.

 

GENERAL CHARACTERISTICS

  • High reliability

  • People and equipment safety

  • According with international standards

  • Compact conception (very reduced dimensions)

  • Ideal for the most adverse environments - Environment friend

  • suitable for ring or radial MV secondary distribution networks

  • Modular construction

  • Extensible on site without  SF6 handling (optional)

  • Internal arc protection system

  • Live cables signaling and phase agreement measure

  • Mechanical and electrical interlocks

  • Low voltage supplementary compartment

  • Easy to install

  • Very easy to operate

  • Increased mechanical and electrical life

  • Without maintenance

  • Remote control and status monitoring

  • Several equipments are available (as optional)

 

DIMENSIONS

 

COMPOSITION

 

  1. Lifting lugs

  2. Earthing switch area

  3. Electrical push buttons (optional)

  4. Door interlock

  5. Ring cables compartment

  6. Low voltage compartment

  7. Status mechanical indicator

  8. Transformer protection switch tripping (opening)

  9. Main switch area

  10. Live cables indication neon lamps

  11. Fuse holder

  12. Cable compartment access door

 

 

AVAILABLE FUNCTIONS

 

FLUOFIX® GC is a compact unit combining the following functions:

  • Network functions, with load break switch

  • Fused transformer function (Tee-off)

  • Circuit breaker transformer function (Tee-off)

It is possible to integrate several functions within the same metallic tank from 1 up to 5 functions. Optionally the unit can be extended on site with additional functions, without any gas handling

 

TECHNICAL DATA

 

ELECTRICAL DATA
Rated voltage kV 12 17.5 24

Insulation level:

 

    - lighting impulse (1,2 / 50 µs)

 

    - power frequency (50 Hz / 1 min.)

 

 

kV peak

 

kV r.m.s.

 

 

75

 

28

 

 

95

 

38

 

 

125

 

50

Rated current: busbar A 630 630 630
Rated current incoming / outgoing A 400 or 630 400 or 630 400 or 630
Rated current protection by fuses A up to 200 up to 200 up to 200
Rated short-time current kA r.m.s.

16 / 20 (3 s);

25 (1 s)

16 / 20 (3 s) 16 (3 s)
Short circuit making current kA peak 50 / 63 40 / 50 40
(ISFG) Mainly active load A 630 630 630
(ISFG) Closed loop A 630 630 630
(ISFG) Cables charging A 25 25 25
AMBIENT TEMPARTURE ºC -5...+40 (other, under reques)

Protection degrees

(IEC 60529 e EN 50102)

-

IP65 (for MV compartments)

IP2XC (mechanism compartments)

IK07

 